HFW-980HA1
Nominal Cooling Capacity(kw):
980
Nominal Heating Capacity(kw):
1059.0
Nominal Refrigeration Input Total Power(kw):
301.5
Nominal Heating Input Total Power(kw):
308.8
Power Supply:
380V/3N~/50Hz
Fan Type:
Axial-flow Low-noise Fan
Refrigerant Type:
R410A
Dimension(mm):
8240*2280*2540
Net Weight(kg):
9370
Gross Weight (kg):
9700
Highlight:

High Light

Highlight:

Holtop vortex air-cooled chiller

,

module-type heat pump unit

,

industrial AHU water chiller

Trading Information
Minimum Order Quantity:
1pc
Price:
Negotiate
Packaging Details:
Carton
Delivery Time:
Negotiate
Payment Terms:
T/T
Supply Ability:
20000PCS/years
Product Description
Top Selling For Holtop Vortex Module-Type Air-Cooled Chilled Water (Heat Pump) Unit
The vortex module-type air-cooled chilled water (heat pump) unit is based on modular technology and uses air as the cooling (heating) medium. It is an integrated central air conditioning equipment that can be used as both a cooling (heating) source and a combined unit. This unit can be combined with fan coil units, cabinet-type, ceiling-mounted air handling units, and fresh air units to form a semi-centralized air conditioning system.
Product Features
  1. Module combination, hierarchical startup: The unit adopts a modular design. When combining modules, there is no need to distinguish between the main and secondary machines. Installation is convenient. The maximum number of units in each group can reach 16, which can meet the load requirements of different buildings, and different series of models can be combined and controlled. The unit has a hierarchical startup function, reducing the startup current of the unit and minimizing the impact on the power grid, without affecting the safety of electrical equipment in the same area.
  2. Intelligent defrosting: The unit detects multiple variables to accurately determine the frosting situation and intelligently selects the best timing to enter or exit the defrosting condition to avoid incomplete defrosting or frequent defrosting problems. The unit with a dual-system design can realize interval defrosting. In harsh environments during heating, manual defrosting can be set.
  3. Flexible application: Unit expansion is convenient and suitable for phased investment. The unit is small in size and can be independently transported, without the need for large lifting and installation equipment. Just install it in a well-ventilated location, no special machine room or cooling water system is required. The end water inlet and outlet design at the unit end is more conducive to reducing the on-site installation space. The end circulation system, in addition to the traditional fixed water flow system, can also be designed as a single pump variable water flow system, and a matching water system frequency control cabinet can be purchased as an option.
  4. Safe operation control: Design multiple safety protection functions to provide comprehensive protection for the unit and the system. The unit is intelligently controlled through multiple variable monitoring to ensure efficient and stable operation.
  5. Fault backup operation: A single unit adopts a dual-compressor design. When one of the compressors fails, the remaining compressors in the system can still operate normally, without affecting the normal use of the entire system.
Technical Specifications
Rated Voltage Three-phase 380V/3N~
Rated Frequency 50Hz
Power Supply Voltage ±10% of the rated voltage
Operating Conditions See Tables 1 to 3
Storage Conditions Environmental temperature: -28 to 85℃
Control Method Remote controller
Fan Type Axial flow low-noise fan
Dimensions Refer to the attached materials
Operating Range of the Unit
Operating condition Outdoor ambient temperature Outlet water temperature of the unit
Cooling 15℃ ≤ Outdoor ambient temperature ≤ 48℃ 5℃ ≤ Water outlet temperature of the unit ≤ 15℃
Heating -15℃ ≤ Outdoor ambient temperature ≤ 21℃ 40℃ ≤ Water outlet temperature of the unit ≤ 50℃
Parameters of Variable Operating Conditions for Refrigeration Systems
Outlet Temperature(℃) Environment Temperature(℃)
25 30 35 40 45
5 1.07 1.00 0.94 0.84 0.81
6 1.10 1.03 0.97 0.87 0.83
7 1.14 1.07 1.00 0.91 0.86
8 1.17 1.10 1.03 0.94 0.88
9 1.20 1.13 1.06 0.98 0.91
10 1.23 1.16 1.09 1.01 0.93
11 1.27 1.19 1.12 1.04 0.96
12 1.31 1.23 1.15 1.07 0.99
13 1.34 1.26 1.17 1.09 1.01
14 1.37 1.29 1.20 1.12 1.03
15 1.41 1.32 1.23 1.14 1.06
Parameters of Variable Operating Conditions for Heating Mode
Outlet Temperature(℃) Environment Temperature(℃)
15 10 7 0 -5 -10
30 1.23 1.10 1.03 0.94 0.88 0.75
35 1.21 1.09 1.02 0.93 0.87 0.75
40 1.20 1.08 1.01 0.91 0.85 0.74
45 1.19 1.07 1.00 0.90 0.84 0.74
50 1.17 1.05 0.98 0.85 0.80 0.74
Large Vortex Modular Air-Cooled Chiller (Heat Pump) Unit Specifications
Model HFW-420HA1 HFW-560HA1 HFW-840HA1 HFW-980HA1 HFW-1120HA1
Nominal cooling capacity 420.0 kW 560.0 kW 840.0 kW 980.0 kW 1120.0 kW
Nominal Heating capacity 454.0 kW 605.0 kW 908.0 kW 1059.0 kW 1210.0 kW
Nominal refrigeration input total power 129.2 kW 172.3 kW 258.4 kW 301.5 kW 344.6 kW
Nominal heating input total power 132.4 kW 176.4 kW 264.8 kW 308.8 kW 352.8 kW
Power supply 380V/3N~/50Hz
Throttle component Electronic expansion valve
Compressor Type Fully enclosed vortex compressor
Compressor Quantity 3 pc 4 pc 6 pc 7 pc 8 pc
Fan Type Axial-flow low-noise fan
Fan Power 1.8x6 kW 1.8x8 kW 1.8x12 kW 1.8x14 kW 1.8x16 kW
Airflow 23500x6 m3/h 23500x8 m3/h 23500x12 m3/h 23500x14 m3/h 23500x16 m3/h
Wind-side heat exchanger Type High-efficiency finned heat exchanger
Water-side heat exchanger Type High-efficiency shell-and-tube heat exchanger
Nominal water flow rate 72.2 m3/h 96.3 m3/h 144.4 m3/h 168.5 m3/h 192.6 m3/h
Steam turbine water resistance 65 kPa
The dimensions of the inlet/outlet pipe connections for the unit DN125 DN125 DN125*2 DN125*2 DN125*2
Refrigerating fluid Type R410A
Refrigerant charge 24.0x3 kg 24.0x4 kg 24.0x6 kg 24.0x7 kg 24.0x8 kg
Dimension (Length x Width x Height) 3540*2280*2540 mm 4700*2280*2540 mm 7080*2280*2540 mm 8240*2280*2540 mm 9400*2280*2540 mm
Weight 4020 kg 5350 kg 8040 kg 9370 kg 10700 kg
Weight 4160 kg 5540 kg 8320 kg 9700 kg 11080 kg

Note:

1. The test conditions for nominal cooling capacity are: water flow rate of 0.172 m³/(h*kW), outlet water temperature of 7°C, and outdoor ambient temperature of 35°C.

2. The test conditions for nominal heating capacity are: water flow rate of 0.172 m³/(h*kW), outlet water temperature of 45°C, and outdoor ambient dry/wet bulb temperature of 7/6°C.

3. The total water pipe for the modular unit combination needs to be fabricated and installed on-site. The factory does not provide it. The pipe diameter and construction must comply with the design standards.

4. When the modular unit is used in actual applications, it can be combined based on the same or different module units as needed. The number of combinations can range from 1 to 16 units. The above table shows the parameters of a single unit.

5. Control accessories need to be ordered separately. The control accessories include a remote controller, user manual, connection cables, etc. The manufacturer reserves the right to change the configuration. Please refer to the factory's configuration when purchasing.