Home > Products >
Industrial Air Handling Units AHU
>
Industrial Air Handling Units AHU vortex module type unit designed to work with fan coil and ceiling mounted air handling units

Industrial Air Handling Units AHU vortex module type unit designed to work with fan coil and ceiling mounted air handling units

Product Details:
Place of Origin: China,Beijing
Brand Name: Holtop
Certification: CE
Model Number: HFW-560HA1
Detail Information
Place of Origin:
China,Beijing
Brand Name:
Holtop
Certification:
CE
Model Number:
HFW-560HA1
Model:
HFW-560HA1
Nominal Cooling Capacity(kw):
560.0
Nominal Heating Capacity(kw):
605.0
Nominal Refrigeration Input Total Power(kw):
172.3
Nominal Heating Input Total Power(kw):
176.4
Power Supply:
380V/3N~/50Hz
Fan Type:
Axial-flow Low-noise Fan
Refrigerant Type:
R410A
Dimension(mm):
4700*2280*2540
Net Weight(kg):
5350
Highlight:

High Light

Highlight:

Industrial Air Handling Units AHU vortex module

,

AHU unit for fan coil systems

,

ceiling mounted air handling units

Trading Information
Minimum Order Quantity:
1pc
Price:
Negotiate
Packaging Details:
Carton
Delivery Time:
Negotiate
Payment Terms:
T/T
Supply Ability:
20000PCS/years
Product Description
Industrial Air Handling Units AHU Vortex Module Type
Vortex module-type unit designed to work with fan coil and ceiling mounted air handling units for comprehensive industrial air conditioning solutions.
Product Overview
The Industrial Air Handling Unit AHU HFW-560HA1 is an advanced vortex module-type air-cooled chilled water (heat pump) unit utilizing modular technology with air as the cooling and heating medium. This integrated central air conditioning equipment serves as both a cooling/heating source and combined unit, designed to work with fan coil units, cabinet-type, ceiling-mounted air handling units, and fresh air units to form semi-centralized air conditioning systems.
Key Features
  • Modular Combination & Hierarchical Startup: Flexible modular design allows combinations without distinguishing between main and secondary machines. Supports up to 16 units per group with hierarchical startup to reduce current impact on power grids.
  • Intelligent Defrosting: Multi-variable detection for precise frost determination and optimal defrost timing. Dual-system design enables interval defrosting with manual override for harsh conditions.
  • Flexible Application: Easy unit expansion suitable for phased investment. Compact size allows independent transport and installation without special equipment or dedicated machine rooms.
  • Safe Operation Control: Multiple safety protection functions with intelligent multi-variable monitoring for efficient, stable operation.
  • Fault Backup Operation: Dual-compressor design ensures continued operation if one compressor fails, maintaining system functionality.
Technical Specifications
Rated Voltage: Three-phase 380V/3N~
Rated Frequency: 50Hz
Power Supply Voltage: ±10% of rated voltage
Storage Conditions: Environmental temperature: -28 to 85℃
Control Method: Remote controller
Fan Type: Axial flow low-noise fan
Operating Range
Operating Condition Outdoor Ambient Temperature Outlet Water Temperature
Cooling 15℃ ≤ Temperature ≤ 48℃ 5℃ ≤ Temperature ≤ 15℃
Heating -15℃ ≤ Temperature ≤ 21℃ 40℃ ≤ Temperature ≤ 50℃
Model Specifications
Model HFW-420HA1 HFW-560HA1 HFW-840HA1 HFW-980HA1 HFW-1120HA1
Nominal Cooling Capacity (kW) 420.0 560.0 840.0 980.0 1120.0
Nominal Heating Capacity (kW) 454.0 605.0 908.0 1059.0 1210.0
Refrigeration Input Power (kW) 129.2 172.3 258.4 301.5 344.6
Heating Input Power (kW) 132.4 176.4 264.8 308.8 352.8
Compressor Quantity 3 4 6 7 8
Nominal Water Flow Rate (m³/h) 72.2 96.3 144.4 168.5 192.6
Dimensions (L*W*H mm) 3540*2280*2540 4700*2280*2540 7080*2280*2540 8240*2280*2540 9400*2280*2540
Weight (kg) 4020/4160 5350/5540 8040/8320 9370/9700 10700/11080
Important Notes
  • Nominal cooling capacity test conditions: water flow rate 0.172 m³/(h*kW), outlet water temperature 7°C, outdoor ambient temperature 35°C.
  • Nominal heating capacity test conditions: water flow rate 0.172 m³/(h*kW), outlet water temperature 45°C, outdoor dry/wet bulb temperature 7/6°C.
  • Modular unit combinations require on-site fabrication of total water piping (not provided by factory).
  • Units can be combined in groups of 1-16 units using same or different module units.
  • Control accessories must be ordered separately and include remote controller, user manual, and connection cables.