| Rated Voltage | Three-phase 380V/3N~ |
| Rated Frequency | 50Hz |
| Power Supply Voltage | ±10% of rated voltage |
| Storage Conditions | Environmental temperature: -28 to 85℃ |
| Control Method | Remote controller |
| Fan Type | Axial flow low-noise fan |
| Operating Condition | Outdoor Ambient Temperature | Outlet Water Temperature |
|---|---|---|
| Cooling | 15℃ ≤ Temperature ≤ 48℃ | 5℃ ≤ Temperature ≤ 15℃ |
| Heating | -15℃ ≤ Temperature ≤ 21℃ | 40℃ ≤ Temperature ≤ 50℃ |
| Model | HFW-420HA1 | HFW-560HA1 | HFW-840HA1 | HFW-980HA1 | HFW-1120HA1 |
|---|---|---|---|---|---|
| Nominal Cooling Capacity (kW) | 420.0 | 560.0 | 840.0 | 980.0 | 1120.0 |
| Nominal Heating Capacity (kW) | 454.0 | 605.0 | 908.0 | 1059.0 | 1210.0 |
| Refrigeration Input Power (kW) | 129.2 | 172.3 | 258.4 | 301.5 | 344.6 |
| Heating Input Power (kW) | 132.4 | 176.4 | 264.8 | 308.8 | 352.8 |
| Compressor Quantity | 3 | 4 | 6 | 7 | 8 |
| Nominal Water Flow Rate (m³/h) | 72.2 | 96.3 | 144.4 | 168.5 | 192.6 |
| Dimensions (L*W*H mm) | 3540*2280*2540 | 4700*2280*2540 | 7080*2280*2540 | 8240*2280*2540 | 9400*2280*2540 |
| Weight (kg) | 4020/4160 | 5350/5540 | 8040/8320 | 9370/9700 | 10700/11080 |
1. Nominal cooling capacity test conditions: water flow rate 0.172 m³/(h*kW), outlet water temperature 7°C, outdoor ambient temperature 35°C.
2. Nominal heating capacity test conditions: water flow rate 0.172 m³/(h*kW), outlet water temperature 45°C, outdoor dry/wet bulb temperature 7/6°C.
3. Modular unit combinations require on-site fabrication of total water piping (not provided by factory).
4. Units can be combined in groups of 1-16 units using same or different module units.
5. Control accessories must be ordered separately and include remote controller, user manual, and connection cables.